Shine Wave UPS

Luminous Sine wave UPS

Being one of the leaders in innovation, design sensibility and sales distribution network, we are offering Power Back Up Solutions and Power Back Up System that includes Power Digital Inverters, Online UPS Systems, Line Interactive UPS Systems, Inverter Batteries (Lead Acid and VRLA).

Features & Protection

  • Micro controller based design
  • Regulated output voltage window during regulated UPS mode
  • Can run single PC up to 8hrs. With 24 V 150 AH battery
  • Selectable battery option
  • Pre-loaded battery management software
  • Charges battery double fast
  • Regulated battery charging from 120 V to 300 V
  • Automatic holiday mode preserves battery charge
  • Advanced digital display
  • Audio alarms on mains fail, Charger fuse blown, battery low and no load shutdown
  • Phase reversal protection
  • Overload with auto re-set
  • Battery Deep Discharge protection with two times reset options
  • Ultra Fast Short Circuit Protection
  • Battery reverse polarity protection
  • Miniature circuit breaker for overload and short circuit protection in mains mode instead of cartridge fuse
  • DC over Voltage protection.

inverter dealers in delhi-ncr
pecifications of SINEWAVE UPS 600/800/1400VA

INPUT Regulated UPS mode
Under Voltage 180 +/- 5 V
Undervoltage Restoration 185 +/- 5 V
Over Voltage 260 +/- 5 V
Over Voltage Restoration 255 +/- 5 V
Unregulated UPS mode
Under Voltage 100 +/- 10 V
Undervoltage Restoration 115 +/- 10 V
Over Voltage 285 +/- 10 V
Over Voltage Restoration 270 +/- 10V
OUTPUT Voltage (UPS Mode) 230 V(Nominal)
Voltage (Mains Mode) Same as Input
Frequency (UPS Mode) 50Hz.±2%
Frequency (Mains Mode) Same as Input (45-55 Hz.)
Overload > 110 %
Transfer Time (typical a.s) 10ms.
BATTERY Type 12V/120AH-150AH Lead Acid Type
Number 1
Typical Recharge Time 10-12 Hrs.
Protection Battery Deep Discharge, Reverse Polarity, DC Overvoltage
LED DISPLAY UPS ON Red
SWITCH ON White
Low Battery Pre-Alarm UPS ON+LOW BATTERY LED BLINKS
Battery Low Red
Mains On Red
Smart Charge Red (Along with Mains On LED)
Overload Red
Short Circuit OVERLOAD RED LED BLINKING
No Load Shut Down Red
Battery Charged Mains On LED steady
MCB Trip Mains On+Smart charge blinking
ALARMS Low Battery Pre-Alarm Beeps every 1.5 Minutes
Low Battery Trip Beeps Continuously for 10 seconds
Overload Beeps Continuously for 10 seconds
Mains to UPS Beeps every 2 seconds for 5 times
Short Circuit Beeps Continuously for 10 seconds
No Load Shut Down Beeps Continuously for 10 seconds
MCB Trip Beeps every 12 minutes
ENVIRONMENTAL Operating Temperature 0-45o C  (32-113 o  F)
Storage Temperature 0-45o C  (32-113 o  F)
Humidity 0-95 % RH non -condensing
*Due to Continuous Product improvements,specs are subject to change without notice.


  Specifications of SINEWAVE UPS 1500VA

INPUT Regulated UPS mode
Under Voltage 180 +/- 5 V
Undervoltage Restoration 185 +/- 5 V
Over Voltage 260 +/- 5 V
Over Voltage Restoration 255 +/- 5 V
Unregulated UPS mode
Under Voltage 100 +/- 10 V
Undervoltage Restoration 115 +/- 10 V
Over Voltage 285 +/- 10 V
Over Voltage Restoration 270 +/- 10V
OUTPUT Voltage (UPS Mode) 230 V(Nominal)
Voltage (Mains Mode) Same as Input
Frequency (UPS Mode) 50Hz.±2%
Frequency (Mains Mode) Same as Input (45-55 Hz.)
Overload > 110 %
Transfer Time (typical a.s) 10ms.
BATTERY Type 12V/120AH-150AH Lead Acid Type
Number 1
Typical Recharge Time 10-12 Hrs.
Protection Battery Deep Discharge, Reverse Polarity, DC Overvoltage
DISPLAY UPS ON ON
Low Battery Pre-Alarm Lo
Battery Low Lo
Mains On AC
Smart Charge CH
Overload OL (Steady)
Short Circuit OL (Blinking)
No Load Shut Down Red
Battery Charged 99%
Over Temperautre th
MCB Trip bt
ALARMS Low Battery Pre-Alarm Beeps every 10 seconds
Low Battery Trip Beeps Continuously for 10 seconds
Overload Beeps Continuously for 10 seconds
Mains to UPS Beeps every 2 seconds for 5 times
Short Circuit Beeps Continuously for 10 seconds
No Load Shut Down Beeps Continuously for 10 seconds
MCB Trip Beeps every 12 minutes
ENVIRONMENTAL Operating Temperature 0-45o C  (32-113 o  F)
Storage Temperature 0-45o C  (32-113 o  F)
Humidity 0-95 % RH non -condensing


Cruze Range

  • Adaptive Battery Charging Control (ABCC) technology to avoid the overcharging of the battery inverter dealers in delhi-ncr
  • Pure Sine Wave Output with low THD in output voltage, reducing the noise and helping in smooth operation of device at output
  • SMT Based Design for product reliability
  • LED Display for describing the product Status
  • Miniature Circuit Breaker (MCB) in order to provide the short circuit at output in mains mode
  • Electronic Protection against short circuit at output in UPS mode
  • “0 Sec” Changeover time from inverter to Mains mode (synchronized changeover)
  • Automatic holiday mode preserves battery charge
  • Thermal Protection for safety against high internal product temperature
  • Very high Load Cold start
  • Reverse Battery polarity protection
  • Reverse Phase Protection
  • No load shutdown feature to protect deep discharge of battery, hence, increasing battery life
  • Intelligent battery low cutoff which adjust the battery low cutoff automatically according to load to maintain the longer battery life
  • Battery reverse polarity protection
  • Miniature circuit breaker for overload and short circuit protection in mains mode instead of cartridge fuse
  • DC over Voltage protection.